Fire Extinguishers in the UAE and Saudi Arabia: Types, Sizes, Civil Defence Rules, Brands
A buyer's guide to fire extinguishers in the UAE and Saudi Arabia: agents and fire classes, ratings and sizes, placement rules, Civil Defence and SASO approvals, maintenance, Gulf heat and the main brands.
Most buildings in the UAE and Saudi Arabia are covered by a mix of multipurpose ABC dry powder units for general areas, CO2 units beside electrical panels, and wet chemical units in commercial kitchens, chosen by fire rating rather than cylinder size. Every unit must carry the right approval for the country: a UAE Civil Defence Certificate of Compliance, or SASO conformity through SABER in Saudi Arabia. Start with the hazards on site, then source fire extinguishers that match them and the local code.
This guide is for facility managers, HSE officers, MEP contractors and procurement teams equipping offices, warehouses, shops, kitchens, plants and sites. It covers the classes of fire and the agent for each, sizes and ratings, how many units to provide and where, what the UAE and Saudi rules say, approvals, maintenance, Gulf conditions, the main brands and an RFQ checklist. ListGCC has not tested any product named here; brand details come from the manufacturers' own sites.
There are five common agent types: water (including water mist), foam, dry powder, carbon dioxide (CO2) and wet chemical, plus clean agent and special Class D powder units for niche risks. Each one is matched to the class of fire it is rated for. Using the wrong one can make a fire worse or put the user at risk.
Agent
Fire classes it is used on
Colour zone (UK and EN 3 practice)
Where it is the wrong choice
Water
Class A (wood, paper, textiles)
Red
Live electrical equipment and flammable liquids
Water mist
Class A, and on many models electrical risks
White body
Check the label: ratings vary by model
Foam
Class A and Class B (liquids)
Pale cream
Cooking oil fires unless the unit carries an F rating
Dry powder (ABC)
Class A, B and C, and electrical
Blue
Rooms with sensitive electronics, because of the corrosive residue
Carbon dioxide (CO2)
Class B and electrical
Black
Class A fires; small closed rooms where people stay after discharge
Wet chemical
Class F (UK) or Class K (US): cooking oils and fats; often Class A too
Canary yellow
Live electrical equipment
Special powder
Class D (combustible metals)
Signal violet
General areas: it is a specialist unit
The colours come from the London Fire Brigade's guidance on BS EN 3 practice: the body of every extinguisher is signal red, with a colour zone of up to 5% of the body surface showing the agent. Clean agent units use a green zone. Read the label rather than rely on colour: it states the agent, the rating and the operating temperature range. The guide to ABC powder, CO2, foam, water and wet chemical extinguishers covers each agent in depth.
Classes of fire: European and US labels
You will see two labelling systems on Gulf projects, because both European (EN 3) and US (UL) listed extinguishers are sold here. They mostly line up, with two differences: Europe has no class for electrical fires, and the cooking oil class is F in Europe and K in the US.
What is burning
EN 2 class (Europe, UK)
US class (OSHA, NFPA)
Solids such as wood, paper, textiles
A
A
Flammable liquids and liquefiable solids
B
B (also covers flammable gases and greases)
Flammable gases
C
Included in B
Energised electrical equipment
No class; the label states suitability
C
Combustible metals such as magnesium, sodium, lithium
D
D
Cooking oils and fats in appliances
F
K
The EN 2 definitions above are as summarised in London Fire Brigade guidance note GN08. The US definitions are in OSHA 29 CFR 1910.155, which defines a Class C fire as one involving energised electrical equipment where the user needs an electrically non-conductive agent.
Sizes and ratings: what the numbers mean
Choose by fire rating, not by kilograms. London Fire Brigade guidance says equipment should be allocated by extinguisher rating, "and not the extinguisher size, weight, or content in litres". The rating comes from standard fire tests (BS EN 3-7 in Europe, UL in the US) and is printed on the label.
EN ratings look like 13A, 34B or 15F. The number is the size of test fire the unit put out, so higher is more capable. A 2.5 kg CO2 unit is rated 34B, according to the same guidance.
UL ratings look like 1-A:10-B:C. Kidde's Pro 110 commercial unit, for example, is UL rated 1-A:10-B:C; ANSUL's K-Guard kitchen unit is rated 2-A:K and Kidde's Pro 10 vehicle unit 10-B:C.
Same size, different rating. Gloria's 6 litre foam extinguisher is rated 21A and 183B, and its 9 litre version 27A and 233B, according to its datasheet. Two 6 kg powder units from different makers can carry different ratings too.
Typical sizes span small units for vehicles (UAE authorities have said a 1 to 2 kg unit is generally enough for a passenger car), 6 kg units such as the all-purpose extinguisher Dubai requires on school buses, 6 and 9 litre foam units for buildings, and wheeled units for larger Class B risks. Write the rating you need into the RFQ, then let suppliers offer the size that achieves it.
How many fire extinguishers do you need, and where?
The number and spacing come from the fire code that applies to the building, applied by your consultant and the civil defence authority. In practice, the answer is at least one suitable unit on every floor, placed on escape routes near exits and close to each specific hazard, with spacing short enough that nobody walks far to reach one.
UAE: the Fire and Life Safety Code and local guidance
The UAE Fire and Life Safety Code of Practice is issued by the UAE Civil Defence under the Ministry of Interior. Its January 2017 update, reported by Khaleej Times, ran to 1,384 pages in Arabic and English. DMCC's health and safety bulletin on extinguishers points readers to Chapter 4 of the code, on fire extinguishers, and summarises the practical rules for its free zone tenants:
Keep extinguishers near a door or exit that can be used as an escape route, and near the hazards they suit.
Mount them not more than 1.5 m above the floor, with at least 30 cm from the bottom of the extinguisher to the finished floor.
Install them on hangers or the manufacturer's brackets, in cabinets or on shelves, free from blocking by storage and equipment.
Train employees: DMCC says at least 10% of employees should be trained in basic fire awareness and extinguisher use.
For construction sites, labour camps and site offices in its jurisdiction, Trakhees (the regulator within Dubai's Ports, Customs and Free Zone Corporation) requires portable extinguishers on each floor, at least one adjacent to the staircase on each level of a multi-storey building, and a travel distance to the nearest extinguisher between 9.15 m and 15.25 m. It also requires the type, capacity and number "as required by Civil Defence". Always confirm with the civil defence authority in your emirate before you finalise a layout.
Saudi Arabia: SBC 801 and Civil Defence
In Saudi Arabia, fire protection requirements sit in SBC 801, the Saudi Fire Code, part of the Saudi Building Code. Its Chapter 9 covers fire protection systems, and the International Code Council's training material for it points designers to NFPA standards for equipment design. The 2024 edition of the Saudi Building Code became mandatory on 30 June 2025, after a 180-day transition announced by the National Committee for the Saudi Building Code, so check that drawings follow the 2024 text. Premises also need a Civil Defence licence, issued through the Salamah portal. Find suppliers that can document compliance among fire extinguisher suppliers in Saudi Arabia.
Reference figures from the standards behind the codes
Because both countries' codes draw on international standards, these figures are useful for a first layout. They are reference points, not a substitute for the code that applies to your building.
Item
Figure
Source
Maximum travel distance, Class A
22.9 m (75 ft)
OSHA 29 CFR 1910.157 (US)
Maximum travel distance, Class B hazard
15.2 m (50 ft)
OSHA 29 CFR 1910.157 (US)
Top of unit, gross weight up to 18.14 kg
Not more than 1.53 m above floor
NFPA 10 figures, as adopted in California rules
Top of unit, heavier than 18.14 kg
Not more than 1.07 m above floor
NFPA 10 figures, as adopted in California rules
Bottom of unit to floor
At least 102 mm
NFPA 10 figures, as adopted in California rules
Travel distance on Dubai sites (Trakhees)
9.15 m to 15.25 m
Trakhees fire extinguisher guideline
UK practice uses BS 5306-8:2023, the code of practice for selection and positioning of portable extinguishers, published on 30 November 2023. Placement, signs and stands are covered in more detail in the guide to extinguisher signs, stands and placement.
Approvals: what the product must carry
UAE: Civil Defence Certificate of Compliance
Every fire and life safety product on the UAE Civil Defence list needs a UAE Civil Defence Certificate of Compliance (CoC), issued by an approved certification body. UL's FAQ on the scheme (revised September 2018) states that one CoC format is accepted by all emirates, that a traditional UL certificate is not accepted on its own, and that testing is needed for each manufacturing location. Portable extinguishers were among the BSI Kitemark categories accepted by the civil defence approval committee in a 2015 Fire Industry Association release. In Dubai, the Emirates Safety Laboratory, launched commercially in April 2022, is described by Dubai Media Office as the official authority to issue compliance certificates for safety products in the emirate. The UAE Civil Defence approval guide covers the process step by step.
Saudi Arabia: the SASO technical regulation
SASO's Technical Regulation for Fire Control Materials and Equipment covers portable extinguishers, steel CO2 cylinders for extinguishers, extinguishing agents and the cabinets that hold extinguishers. According to SASO's guide to the regulation, it was approved in August 2019, applied at ports and factories from 1 May 2020 and in the market from 31 October 2020. Products are registered on SABER, assessed under conformity model Type 3, and need a product Certificate of Conformity plus a shipment certificate for each consignment. The guide lists the type tests for portable extinguishers, including leakage over 21 days, a 28-day humid ageing cycle, hydraulic pressure, burst, vibration and extinguishing performance.
Maintenance in brief
Plan for monthly visual checks by the building team, an annual service by a competent contractor, and extended servicing or pressure testing at longer intervals set by the standard and the authority. SASO's guide describes inspection at intervals of about 30 days, annual maintenance and extra procedures at intervals of no more than five years. In the UAE, owners must keep fire fighting equipment under a maintenance contract with a contractor approved by civil defence; Abu Dhabi Civil Defence reminded owners in July 2023 of an AED 10,000 fine for having no valid contract. The full routine is in the extinguisher maintenance and refill guide.
Gulf conditions: heat, humidity, dust and sun
Temperature range. Every extinguisher has a rated operating range on its label, and the upper limit varies. Gloria's foam units are rated 5 °C to +60 °C; Amerex lists -65 °F to 120 °F (about 49 °C) for its ABC units and -22 °F to 120 °F for its CO2 units. Check the range against where the unit will sit: outdoor cabinets, plant rooms, container offices and vehicle cabins in summer.
Humidity and powder. SASO's guide warns that powder can absorb harmful amounts of moisture from humid air, so powder units should only be opened in the driest conditions available and for the shortest time. Different powders must never be mixed, as some react to produce water and CO2.
Corrosion. Coastal sites and wash-down areas corrode cylinders and brackets. SASO's maintenance table says lightly corroded units should be discarded or pressure tested, and badly corroded ones discarded. Ask for weather-resistant coatings and cabinets outdoors.
Sun and dust. Labels fade and gauges become hard to read. Cabinets protect units, but must stay visible and signed.
Fire extinguisher brands in the UAE and Saudi Arabia
The brands below make portable extinguishers and are listed in alphabetical order, not ranked. What matters for your order is the approval of the specific model in your country, the rating and the service support.
Amerex
Amerex was founded in 1971 and is headquartered in Trussville, Alabama, as part of the McWane group. Its hand portable range includes ABC and Purple K dry chemical, CO2, Class K wet chemical, Class D, water mist and Halotron clean agent units, and it also makes wheeled extinguishers and vehicle systems. It suits buyers specifying UL-listed equipment.
ANSUL
ANSUL is a Johnson Controls brand. Its K-Guard kitchen extinguisher is charged with ANSULEX Low pH agent, is designed for fires in cooking vegetable or animal fats in commercial cooking equipment, and carries a 2-A:K rating to UL 8 and 711 and NFPA 10.
Ceasefire
Ceasefire is an Indian manufacturer with an address in New Delhi and manufacturing works in Dehradun. Its range lists ABC powder, CO2, water and foam, clean agent, water mist, wet chemical, metal fire, automatic and home and car units, and its site lists exports to the UAE and Saudi Arabia.
Gloria
Gloria (GLORIA GmbH, Wadersloh, Germany) marked eight decades in fire protection in 2025. It makes portable and mobile extinguishers, including fluorine-free foam units, and publishes ratings and temperature ranges on its datasheets.
Kidde
Kidde says it has worked in fire safety for more than 100 years. Its commercial Pro range on kidde.com includes the Pro 110 (UL 1-A:10-B:C) for general areas and the Pro 10 (UL 10-B:C) for vehicles, supplied with a strap bracket.
NAFFCO
NAFFCO was founded in Dubai and has its world headquarters in Jebel Ali Free Zone, with more than 11 million square feet of manufacturing facilities and exports to over 100 countries, according to its site. Its range covers CO2, dry chemical powder, water, foam, clean agent, wet chemical and mobile extinguishers, with certifications it lists from bodies such as UL, FM, BSI and LPCB. Dubai Media Office reported that NAFFCO was the first company accredited by the Emirates Safety Laboratory.
SFFECO
SFFECO was established in 1983 and is headquartered in Riyadh, with branches in Jeddah, Dammam and Madinah and manufacturing plants in Riyadh and Dubai, according to its site. It supplies extinguishers alongside wider fire fighting equipment.
If the same package includes hose reels, cabinets or hydrant valves, compare suppliers of fire fighting equipment; if you are also replacing detection, see fire alarm systems.
Fire extinguisher RFQ checklist
List each area and its hazard (offices, electrical rooms, kitchens, fuel or chemical stores, server rooms, vehicles) and the fire classes present.
State the required rating per location (for example 21A 183B, or 1-A:10-B:C), not just the size.
Name the agent: ABC powder, CO2, foam, water, water mist, wet chemical or Class D.
Ask for the approval for the exact model and factory: the UAE Civil Defence CoC (and ESL where Dubai requires it), or the SASO Certificate of Conformity on SABER for Saudi Arabia.
Confirm the standard and listing on the label (BS EN 3 Kitemark, UL, or other).
Check the operating temperature range against the hottest location the unit will occupy.
Specify brackets, stands or cabinets, and signs, for every location.
Ask for the service plan: first-year inspection, annual service, extended service and pressure testing intervals, and who will do it.
Confirm the contractor's civil defence approval for installation and maintenance.
Ask for spare units during servicing, refill pricing and the manufacturer's warranty.
For a pre-handover check or an existing building, a fire and safety audit can confirm the layout before you buy. To get quotes from several suppliers at once, post your requirement with the location schedule and ratings.
Go deeper
Each of these guides takes one question from this page further.
Five agent types cover almost every building: water (including water mist), foam, dry powder, carbon dioxide and wet chemical. Clean agent units and special Class D powder units serve niche risks such as sensitive equipment and combustible metals. Each type is rated for specific classes of fire, A to F in Europe or A, B, C, D and K in the US, and the rating on the label matters more than the cylinder size.
What is the UAE FLS code of practice?
The UAE Fire and Life Safety Code of Practice is the national fire code issued by the UAE Civil Defence under the Ministry of Interior. It sets requirements for fire protection systems, materials and equipment, including a chapter on fire extinguishers, and is applied by the civil defence authority in each emirate. Its 2017 update ran to 1,384 pages in Arabic and English. Confirm the current edition with civil defence before you design.
Which is better, ABC or CO2 fire extinguisher?
Neither is better everywhere. An ABC dry powder unit covers solids, liquids, gases and electrical fires and suits general areas, but leaves a residue. A CO2 unit leaves no residue and suits electrical panels and server rooms, but is not intended for Class A fires and works by displacing oxygen. Many buildings use both: ABC on corridors and CO2 beside electrical equipment.
What is a CO2 extinguisher?
A CO2 extinguisher holds carbon dioxide, which OSHA defines as a colourless, odourless, electrically non-conductive inert gas that puts out fire by reducing the oxygen or fuel vapour concentration around it. It is used on flammable liquid and electrical fires. In the UK colour scheme it carries a black colour zone, and a 2.5 kg unit is rated 34B.
Do fire extinguishers need Civil Defence approval in the UAE?
Yes. Fire and life safety products on the civil defence list need a UAE Civil Defence Certificate of Compliance issued by an approved certification body, and one format is accepted in all emirates. A UL listing or Kitemark is supporting evidence, not the approval itself. In Dubai, ask whether the product group also needs an Emirates Safety Laboratory certificate.
What approval do fire extinguishers need in Saudi Arabia?
Portable extinguishers fall under SASO's Technical Regulation for Fire Control Materials and Equipment, in force in the market since 31 October 2020. The supplier registers the product on SABER, obtains a product Certificate of Conformity through an accepted conformity assessment body, and then a shipment certificate for each consignment. The premises themselves need a Civil Defence safety licence through Salamah.
How often should a fire extinguisher be serviced?
Check every unit visually about once a month and have it serviced by a competent, approved contractor once a year. Extended servicing, discharge and pressure testing follow at longer intervals: SASO's guide sets extra procedures at no more than five years, and US rules set hydrostatic tests at 5 or 12 years depending on type. Record every check on the tag and in a log.
Each fire extinguisher type explained for Gulf buyers: how ABC powder, CO2, foam, water, water mist, wet chemical and Class D units work, what they are rated for, colour codes and where each is wrong.
Where to put fire extinguishers and how to mark them: travel distances, mounting heights in UAE and NFPA guidance, ISO 7010 F001 signs, brackets, stands and cabinets, SASO rules for cabinets, and Gulf heat.
How to keep fire extinguishers in service in the UAE and Saudi Arabia: the monthly check, annual service, five-year work, hydrostatic test intervals, refilling, tags and records, approved contractors and cost drivers.