Voltage transformers in the UAE step high system voltage down to a safe secondary level for meters, protection relays and synchronising equipment in switchgear and substations. This page covers inductive and capacitive types, class, burden and voltage factor, IEC 61869-3, utility approval, climate effects, and what drives price and lead time.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified voltage transformers suppliers who quote for your order directly.
Tell us about voltage transformers in UAE and receive competitive quotes from verified suppliers — free, fast, and no obligation.
How step-up and step-down transformers differ, where each is used at Gulf power plants, solar sites and buildings, and what isolation, auto, K-rated, earthing and instrument transformers do.
How to select a current transformer: ratio, metering and protection accuracy classes, burden, knee point, core balance CTs for earth fault, construction types and SEC requirements.
A voltage transformer (VT, also called a potential transformer) reduces a high system voltage to a safe, standard secondary level, commonly 110 V or 110/√3 V, for meters, protection relays and synchronising equipment. In the UAE VTs are fitted in 11 kV and 33 kV switchgear, generator panels, and 132 kV and higher outdoor substations. They are part of the transformers family for UAE projects and work alongside current transformers, which supply the current signal for the same meter or relay. The big units they monitor are covered under power transformers.
IEC 61869-3, edition 1.0 published on 13 July 2011, covers new inductive voltage transformers used with electrical measuring instruments and protective devices from 15 Hz to 100 Hz. It replaced IEC 60044-2 and is read together with IEC 61869-1:2007.
| Type | Typical UAE use | Points to specify |
|---|---|---|
| Cast resin inductive VT (fused or unfused) | 11 kV and 33 kV switchgear and ring main units for metering and protection | Primary and secondary voltage, accuracy class, burden, voltage factor, primary fuses |
| Single-pole insulated VT | Phase-to-earth measurement in switchgear panels | Insulation level, rated voltage factor, residual voltage winding |
| Oil-insulated outdoor inductive VT | 132 kV and 220 kV substations | Highest voltage, creepage, hermetic design, cores for metering and protection |
| Capacitive voltage transformer (CVT) | Higher-voltage lines where a capacitor divider is cheaper than inductive design | Capacitance, intermediate transformer, transient response, line-carrier use |
| Combined CT and VT units | Compact HV substations with limited space | Ratings of each element, shared housing, standard for combined units |
| Station service VT | Auxiliary supply from the HV system | Power rating, voltage, class |
Hitachi Energy lists inductive and capacitive voltage transformers, combined current and voltage units, and station service voltage transformers. Its PV123 inductive unit is rated for a highest system voltage of 123 kV at 50 Hz, built to IEC 61869-3, hermetically sealed with PCB-free oil, and described as resistant to ferromagnetic resonance with a service life over 25 years. For metering applications the VT feeds the meters described under energy meters and monitoring, and it normally sits in medium-voltage switchgear.
Choose a VT from its primary and secondary voltage, accuracy class, burden, rated voltage factor and insulation level. Wrong choices show up as wrong billing, relays that mis-operate or VTs that overheat or fail during earth faults.
Gulf conditions work on the insulation, the sealing and the secondary wiring of VTs. Dust and salt on outdoor housings are the most common cause of surface discharge, while heat in panel rooms ages resin and fuses.
VTs in the UAE are bought to IEC 61869 and accepted by the utility or project consultant at submittal. As of 2026 we could not confirm from the sources we opened that a federal product certificate is required for instrument transformers, so confirm with MoIAT or a notified body for low-voltage items.
| Requirement | Applies to | Authority or owner |
|---|---|---|
| IEC 61869-3:2011 (edition 1.0) | Inductive voltage transformers for measurement and protection | IEC, via the specification |
| Utility metering specification | Revenue metering VTs and test procedures | DEWA, Abu Dhabi, Sharjah and federal utilities |
| Relay and meter maker data | Required class and burden | Relay and meter manufacturers |
| ADNOC Supplier Hub registration | Supply to ADNOC group sites | ADNOC |
| ICV certificate | Tender scoring in national and company projects | MoIAT, National In-Country Value Programme |
When the VT comes inside imported switchgear, the ECAS and EQM conformity guide explains which electrical products need UAE certification.
Medium-voltage VTs normally arrive inside switchgear from the panel builder, while HV and EHV units come directly from the instrument transformer maker. Ask for type test reports and routine test certificates, not just the catalogue class.
Also check whether the exact design is accepted by your utility, the secondary terminal arrangement, the fuse or MCB provision and the polarity marking. Our sourcing guide for the UAE and Saudi Arabia covers vetting. To compare offers, post your requirement with voltages, class, burden, insulation level, indoor or outdoor and quantity.
Price follows voltage level, class, number of secondary windings and insulation type. MV resin VTs are modest items, while a multi-core HV VT or CVT is engineered and priced individually.
Fix VT data in the first switchgear enquiry. Late changes to voltage factor or burden restart manufacturing.