Current transformers in the UAE scale large primary currents to 1 A or 5 A for meters and protection relays in switchgear, kiosks and generator panels. This page covers CT types, ratio, accuracy class and burden, IEC 61869-2, utility metering rules, heat and humidity effects, and what drives price and lead time.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified current transformers suppliers who quote for your order directly.
Tell us about current transformers in UAE and receive competitive quotes from verified suppliers — free, fast, and no obligation.
How step-up and step-down transformers differ, where each is used at Gulf power plants, solar sites and buildings, and what isolation, auto, K-rated, earthing and instrument transformers do.
How to select a current transformer: ratio, metering and protection accuracy classes, burden, knee point, core balance CTs for earth fault, construction types and SEC requirements.
A current transformer (CT) reduces a large primary current to a small, standard secondary current, usually 1 A or 5 A, so meters and protection relays can read it safely. In the UAE CTs go into switchgear, metering kiosks, generator panels and main distribution boards. They sit in the transformers family for UAE projects, next to the voltage transformers that give the matching voltage signal. The main units they protect are covered under power transformers and distribution transformers.
IEC 61869-2, edition 1.0 published on 18 September 2012, is the standard for newly manufactured inductive current transformers used with measuring instruments or protective devices at rated frequencies from 15 Hz to 100 Hz. It replaced IEC 60044-1 and IEC 60044-6, so older specifications that still quote the 60044 numbers are asking for the same product under its former name.
| Type | Typical UAE use | Points to specify |
|---|---|---|
| Ring (window) and bar-primary CTs | Low-voltage switchboards, motor control centres and generator incomers | Ratio, accuracy class, burden in VA, window size or busbar dimensions |
| Split-core CTs | Retrofit energy metering on live cables and busbars in existing buildings | Accuracy class, secondary output (1 A, 5 A or low-level), opening size |
| Cast resin medium-voltage CTs | 11 kV and 33 kV switchgear for metering and protection | Insulation level, short-time current, metering and protection cores |
| Oil or gas-insulated outdoor CTs | 132 kV and above grid substations | Highest voltage, creepage for pollution, cores for revenue metering, protection and differential schemes |
| Zero-sequence (core balance) CTs | Earth fault protection on cable feeders | Window diameter, ratio, relay input |
| Low-power current sensors | Digital substations and compact MV switchgear | Output signal type, compatible relay or merging unit |
Hitachi Energy lists current transformers, inductive and capacitive voltage transformers and combined units from 25 kV to 800 kV for measurement, protection and control. For low-voltage metering, Socomec supplies split-core CTs to pair with its DIRIS and COUNTIS meters. Where CTs feed power meters, the data side is covered on the energy meters and monitoring page, and in the panel the CT shares space with circuit breakers and low-voltage switchgear.
Choose a CT from four numbers: primary ratio, accuracy class, rated burden and, for protection, the accuracy limit. If any one is wrong the meter reads off or the relay fails to see a fault because the core saturates.
Combined metering and protection cores are normal, but each core needs its own class and burden on the datasheet. Give the supplier the relay and meter model numbers, not just the target class.
CTs have no moving parts, so the Gulf climate acts on insulation, enclosures and terminals rather than on the core. The common faults are overheated secondary wiring, tracking on contaminated insulators and moisture in terminal boxes.
CTs in the UAE are bought to IEC 61869 and accepted by the utility that owns the metering point, with the consultant checking class, burden and test certificates at submittal. As of 2026 we could not confirm from the sources we opened that a federal product certificate is required for instrument transformers, so check with MoIAT or a notified body for low-voltage items.
| Requirement | Applies to | Authority or owner |
|---|---|---|
| IEC 61869-2:2012 (edition 1.0) | Inductive current transformers for measuring and protection | IEC, via the specification |
| IEC 61869-1 general requirements | All instrument transformer parts | IEC |
| Utility metering specification | Revenue metering CTs and test procedures at the point of supply | DEWA, Abu Dhabi, Sharjah and federal utilities |
| Relay and meter manufacturer data | Burden, knee-point voltage and accuracy limit for protection | The relay and meter makers |
| ICV certificate | Tender scoring in national and company projects | MoIAT, National In-Country Value Programme |
Where CTs are part of imported switchgear, the ECAS and EQM conformity guide explains which electrical products need UAE certification.
Match the supplier to the voltage level: electrical distributors stock standard low-voltage CTs, while medium-voltage and grid CTs come from the switchgear builder or the instrument transformer maker with test certificates. Genuine type test reports and routine test certificates matter more than the catalogue class.
Ask for the routine test certificate for each CT, the ratio and polarity marking, and the wiring diagram for each core. Our sourcing guide for the UAE and Saudi Arabia covers vetting. To compare offers, post your requirement with ratio, class, burden, voltage level, mounting and quantity.
Price follows voltage level, number of cores, accuracy class and short-time rating. Low-voltage ring CTs are low-cost catalogue items, while an HV outdoor CT with several cores is engineered and priced by the unit.
When CTs are part of a switchgear order, the panel builder usually carries the lead time, so specify CT data in the first panel enquiry and avoid late changes.