Dry-type transformers in Saudi Arabia are air-cooled, resin-insulated units used in hospitals, towers, airports and data centres where oil is unwelcome. This page covers cast resin types, how room heat, dust and humidity change the specification, GSO IEC 60076-11, SEC and Aramco approval, SABER, and price and lead time.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified dry type transformers suppliers who quote for your order directly.
Tell us about dry type transformers in Saudi Arabia and receive competitive quotes from verified suppliers — free, fast, and no obligation.
Dry-type transformers are air-cooled units insulated with cast resin or varnish, used in Saudi Arabia where oil is unwelcome: hospitals, airport terminals, towers in Riyadh and Jeddah, metro stations and data centres. They belong to the transformers family for Saudi Arabia. Oil-filled units at the same ratings are on the distribution transformers page, and the heavy grid units on the power transformers page.
The reference standard is IEC 60076-11, which the Gulf Standards Organization has adopted as a current GSO edition approved on 12 May 2022, based on IEC 60076-11:2018. It covers dry-type power transformers up to 72.5 kV highest voltage with at least one winding above 1.1 kV, and excludes gas-filled units, instrument transformers, welding and traction types.
| Construction | Saudi application | Specification points |
|---|---|---|
| Vacuum-cast resin in a ventilated enclosure | Hospital, hotel, tower and mall substations in Riyadh, Jeddah and Makkah | Insulation class, IP rating, environmental, climatic and fire behaviour classes, temperature sensors |
| Cast resin with cooling fans | Rooms where peak demand exceeds natural-air rating | Rating with and without fans, fan failure alarm, noise |
| Varnish-impregnated open units | Clean industrial rooms and drive or generator duty | Moisture protection, class of insulation, dust control |
| Harmonic-duty units | Data centres, chillers and variable speed drive incomers | Harmonic loading, shielding, extra thermal margin |
| Packaged substation with dry-type transformer | Compound, camp and construction supply | Enclosure ventilation, solar load, 60 Hz rating |
Schneider Electric describes its Trihal range as cast resin dry-type transformers up to 15 MVA and 36 kV. Siemens sells its GEAFOL cast resin range through its energy business. The incoming side joins medium-voltage switchgear, and the secondary feeds low-voltage switchgear. Check the nameplate frequency, because the Saudi network runs at 60 Hz.
A dry-type transformer relies on room air for cooling, so Saudi room temperature, shamal dust and coastal condensation drive the specification. Treat the room and the transformer as one system.
Ask the maker for full-load losses in kilowatts and design ventilation or cooling to remove them at the hottest summer room temperature. Riyadh and the Eastern Province have long, intense summers, and plant rooms with chillers or generators add heat. Specify winding temperature sensors with alarm and trip outputs, and fan control where fans are offered. Do not let the room design assume the outdoor annual average.
Fine dust enters through louvres and settles in winding ducts, which raises temperature and can lead to surface tracking when damp. Use filtered inlets, sealed doors and a cleaning plan before the summer peak. The 2018 edition of IEC 60076-11 links environmental class to the installation location, so state the class instead of accepting a default.
In Jeddah, Yanbu, Jubail and Dammam, humid air can condense on a cold, de-energised transformer in a warm room. Ask for anti-condensation heaters or keep the room dry through construction, and agree a drying-out check before first energisation. The 2018 edition added new climatic classes and an altitude correction for dielectric and thermal requirements, relevant for highland sites.
Resin removes the oil fire pool, but the room still needs fire separation and detection. Fire behaviour classes in the standard stop at 1,000 kVA, so for larger ratings ask the project fire engineer which tests apply.
Saudi dry-type transformers are designed to IEC 60076-11 or the GSO adoption of it, accepted by SEC, Aramco or the project owner, and imported through SABER if the product is regulated. As of 2026 we could not confirm from the sources we opened whether a dry-type transformer is on a SABER regulated list, so ask your clearing agent or a SASO-approved body.
| Requirement | Applies to | Authority or owner |
|---|---|---|
| GSO IEC 60076-11 (approved 12 May 2022), based on IEC 60076-11:2018 | Dry-type power transformers up to 72.5 kV highest voltage | Gulf Standards Organization |
| Environmental, climatic and fire behaviour classes | Datasheet choice of enclosure and insulation | Project designer |
| SEC specification and approved manufacturer status | Units on or connecting to the SEC network | Saudi Electricity Company |
| Aramco supplier registration and qualification | Supply to Aramco and its contractors | Saudi Aramco |
| SABER product and shipment certificates | Regulated imports | SASO, through certification bodies |
Aramco says all suppliers must register, that Saudi-based suppliers register through its e-Marketplace platform, and that registration does not guarantee business. SABER issues a product certificate and then a shipment certificate valid for that shipment only. Read our guide to SASO and SABER certificates for industrial equipment for the sequence.
Saudi buyers get dry-type transformers from international groups with regional offices, from local factories, and from switchgear builders that package them into substations.
Buy from the manufacturer, its Saudi office or an authorised panel builder. Ask for type test reports, the classes tested, the loss guarantee, sensor and fan options and the 60 Hz rating. Our sourcing guide lists vetting steps. To receive comparable offers, post your requirement with kVA, voltage, enclosure, room ambient and loss targets.
Price follows rating, voltage, losses and enclosure, and lead time follows the factory slot and testing. Cast resin costs more per kVA than oil, but it can cut bunds, fire walls and room size.
Freeze kVA, voltage and enclosure before drawing approval, because changes after release restart the manufacturing slot.
A buyer's guide to transformers in the UAE and Saudi Arabia: types, data sheet ratings, IEC 60076, DEWA and SEC specifications, losses, Gulf heat derating, makers and what to put in an RFQ.
When to specify a cast resin dry-type transformer and when an oil-immersed one: fire and indoor rules, cooling at Gulf ambients, SEC loss tables, monitoring, maintenance and cost drivers.