Surge protection devices in the UAE limit lightning and switching overvoltages on power systems by diverting surge current to earth. This page explains Type 1, 2 and 3 SPDs, where to install each in a building, how UAE heat and solar plants affect them, which IEC and local rules apply, and how to choose a supplier.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified surge protection devices suppliers who quote for your order directly.
Tell us about surge protection devices in UAE and receive competitive quotes from verified suppliers — free, fast, and no obligation.
A surge protective device (SPD) limits transient overvoltages from lightning and switching by diverting surge current to earth, so that the voltage reaching equipment stays below what its insulation can withstand. In the UAE it is specified for main and sub-main boards in towers, data centres, hospitals, district cooling plants, telecom sites and solar plants, and it belongs to the circuit protection category in the UAE. The table lists the types buyers order.
| Type | Typical use in the UAE | Key specification points |
|---|---|---|
| Type 1 or Type 1+2 (class I tested) | Main incomer of buildings with a lightning protection system or overhead supply | Impulse current Iimp (10/350 waveform) per pole, protection level Up, earthing system |
| Type 2 (class II tested) | Sub-distribution boards, plant rooms and floor boards | Discharge current In and Imax (8/20 waveform), Up, replaceable cartridges |
| Type 3 | Close to sensitive equipment such as controllers and IT racks | Low Up, plug or terminal fit, coordination with upstream devices |
| DC and photovoltaic SPDs | Rooftop and ground solar arrays, inverters, battery systems | Maximum DC voltage, string configuration, remote alarm |
| Data, signal and telecom protectors | CCTV, BMS, instrument loops, antennas | Signal voltage, bandwidth, connector or terminal |
SPDs sit in the same boards as circuit breakers, are backed up by fuses and fuse links or breakers, and protect the loads switched by relays and contactors. Their housings are described under switchgear and panels in the UAE.
Install a Type 1 or Type 1+2 device at the supply origin, a Type 2 device in downstream distribution boards, and a Type 3 or equipment-level device close to critical loads. Schneider Electric's UAE support note says Type 1 devices are normally connected after the main breaker, and that connection before the main breaker is sometimes allowed for Type 1 only after a case-by-case study.
That study needs the earthing system, the network voltage and the number of poles, the short-circuit current, the SPD type, the local regulatory requirements and the kind of loads. Legrand's technical guidance adds that one SPD rarely gives enough protection if its protection level Up is above 1.2 kV, and that overvoltage values downstream of an SPD can double over distances beyond 10 m because of resonance. Equipment insulation is typically 2.5 kV for most electrical and electronic equipment and about 1.5 kV for domestic appliances, which is why a second stage near sensitive equipment is common.
Legrand also gives a rule of thumb for lightning protection systems: where a lightning protection system exists or a risk assessment has been carried out to IEC 62305, SPDs are generally needed at the main board (Type 1 or 1+2) and at distribution boards (Type 2), and for lightning protection level I the minimum Iimp is 25 kA per pole. This guidance is general, and local rules and project specifications override it.
SPDs are passive until a surge arrives, but they age under repeated surges and heat, and a hot closed board shortens the life of the metal-oxide elements. Check the maker's ambient limit: Chint's NU6-I+II combined Type I and II device lists an ambient range of minus 5 to plus 40 degrees C, so a board that regularly exceeds 40 degrees C needs cooling or a device with a wider rating.
As of 2026, UAE specifications refer to IEC 61643-11 for SPD products and to IEC 62305 for lightning protection, with each emirate's installation rules applying on site. The 2022 MoIAT regulated-products list I read has no SPD row, so confirm with MoIAT or the supplier whether a model needs ECAS registration, and read the project specification and the consultant's requirements.
| Requirement | Applies to | Authority or source |
|---|---|---|
| IEC 61643-11 (Edition 2.0, published 18 June 2025) | SPDs connected to AC power systems rated up to 1,000 V RMS, at 50/60 Hz | IEC; common requirements now in IEC 61643-01 |
| IEC 62305 series (parts 1 to 4) | Lightning protection risk assessment and systems | IEC |
| Electricity Wiring Regulations 2020 | Installations in Abu Dhabi, with tables updated to BS 7671, 18th edition | Department of Energy Abu Dhabi |
| Dubai installation rules | Installations in Dubai | DEWA; confirm the current edition |
| Product conformity schemes | Regulated electrical products | MoIAT, ECAS and EQM |
The Department of Energy announcement says the 2020 edition came into force on 1 April 2020 and does not itself discuss SPDs, so read the regulation text with your designer. Our guide to ECAS and EQM product conformity explains the product schemes.
SPDs are supplied by electrical wholesalers, panel builders, manufacturer offices and specialist lightning protection contractors. Prefer a supplier that can give the test report, the impulse and protection level data and the instructions for backup protection.
Brands on ListGCC with SPD ranges that I checked include Schneider Electric, ABB with the OVR family, Siemens with SENTRON overvoltage protection, Legrand, Chint with the NU6 range, and OBO Bettermann with the V50 combination arrester. Use the sourcing guide for supplier checks, and post your requirement to receive quotes.
Price depends on Type (a Type 1 device costs more than a Type 2), the Iimp or In rating, the number of poles, the earthing system, the DC voltage for solar, and extras such as remote alarm contacts. Standard Type 2 modules are usually stocked; high-energy Type 1+2 devices, DC solar types and special voltages are more often ordered. Ask for lead time per catalogue number and include the backup fuse or breaker in the order.