Surge protection devices in Saudi Arabia protect plant electronics, drives and instruments from lightning and switching surges. This page explains Type 1, 2 and 3 coordination, how Saudi heat, 60 Hz systems and solar parks affect selection, which GSO, IEC and SASO references apply, and how to choose a supplier, price and lead time.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified surge protection devices suppliers who quote for your order directly.
Tell us about surge protection devices in Saudi Arabia and receive competitive quotes from verified suppliers — free, fast, and no obligation.
A surge protection device is a component that clamps transient overvoltages caused by lightning or switching and sends the surge current to earth, protecting drives, PLCs, UPS units, instruments and electronics. Saudi buyers specify it for substations, refineries, petrochemical plants, solar parks, telecom towers, hospitals and data centres, and it is covered in the circuit protection category in Saudi Arabia.
| Type | Where it is used in the Kingdom | What to specify |
|---|---|---|
| Type 1 and Type 1+2 | Main boards of plants and buildings with lightning protection or overhead lines | Iimp per pole, Up, voltage and earthing system |
| Type 2 | Distribution boards, MCCs and plant room boards | In and Imax, Up, plug-in cartridges, alarm |
| Type 3 | Next to sensitive controllers and communication equipment | Low Up, fit, coordination |
| Photovoltaic and DC SPDs | Solar parks and rooftop arrays | Maximum DC voltage, string design |
| Signal and data protectors | Instrument loops, CCTV, control networks | Signal level, connector, bandwidth |
Surge protection is coordinated with circuit breakers, backed by fuses and fuse links and applied in boards that also hold relays and contactors. Boards are described under low-voltage switchgear in Saudi Arabia.
Coordinate by placing a high-energy device at the supply origin, a Type 2 device in downstream boards and a lower-voltage device near sensitive equipment, so that each stage handles what the previous one lets through. Legrand's guidance states that a single SPD seldom gives effective protection if its Up exceeds 1.2 kV, and that downstream overvoltage can double over distances beyond 10 m.
The test waveforms define the types: Legrand lists Type 1 as tested with a 10/350 microsecond impulse current (Iimp) and Type 2 with an 8/20 microsecond discharge current. Where a lightning protection system exists, the guidance gives minimum Iimp per pole by protection level, 25 kA for level I. Schneider Electric's note adds that a Type 1 device is normally connected after the main breaker, and that connection before it is only considered case by case after studying the earthing system, voltage, short-circuit current and local requirements.
Chint's NU6-I+II shows a combined Type I and II device: 12.5 kA Iimp from line to earth, Up not more than 1.5 or 1.8 kV, plug-in modules and a 125 A gL/gG fuse as recommended backup. Compare these figures with your lightning risk assessment, not with the catalogue headline.
Treat the SPD as one of three layers. Legrand describes protection against lightning as resting on a lightning protection system that catches strikes and leads the current to earth, surge protective devices that protect equipment, and a well-designed earthing system. A high-quality SPD on a poor earth connection performs poorly, so ask the earthing designer for the resistance values and keep SPD connecting leads short and straight, in line with the maker's installation instructions.
Heat, salt and a weak supply all shorten SPD life if ignored. Chint's NU6-I+II lists an ambient range of minus 5 to plus 40 degrees C and has ageing and overheating protection with a visual indicator, so a board in Riyadh or Dammam that exceeds 40 degrees C needs cooling or a device with a wider rating.
As of 2026, surge protection devices in Saudi Arabia are specified to IEC 61643-11 or its Gulf adoption, with lightning protection to IEC 62305, and imported electrical products are processed through SASO and SABER. The GCC Standardization Organization store lists GSO IEC 61643-11:2014, based on IEC 61643-11:2011, as the current Gulf edition of the standard, approved on 25 December 2014.
| Requirement | Applies to | Authority or source |
|---|---|---|
| GSO IEC 61643-11:2014 (Gulf adoption of IEC 61643-11:2011) | SPDs connected to low-voltage power systems | GSO |
| IEC 61643-11 Edition 2.0 (2025) | AC SPDs up to 1,000 V RMS, 50/60 Hz | IEC |
| IEC 62305 series | Lightning risk assessment and protection systems | IEC |
| SABER registration | Imported products within SASO regulations | SASO |
| Project and utility specifications | Aramco, SEC and consultant requirements | Owner or consultant |
The SASO IECEE certificate page I read does not list SPDs among its example products, so ask SASO or your SABER agent how your model is classified. The Saudi Building Code electrical requirements and utility rules were not confirmed from an official source for this page, so ask your design consultant for the current clause. Our guide to SASO and SABER certificates explains the documents.
SPDs are sold by electrical wholesalers, panel builders, manufacturer subsidiaries and lightning protection specialists in Riyadh, Jeddah and Dammam. Ask for the type test report, the stated Iimp or In, the voltage protection level and the required backup device.
Makers on ListGCC with SPD ranges that I checked are Schneider Electric, ABB with the OVR family, Siemens with SENTRON overvoltage protection, Legrand, Chint with NU6 devices, and OBO Bettermann with V50 combination arresters. The sourcing guide covers supplier checks, and you can post your requirement for quotes.
Type, Iimp or In rating, pole count, earthing system, DC voltage and alarm contacts set the price. Type 2 modules are normally easier to find than Type 1+2 high-energy devices and DC solar types. Ask for lead time per catalogue number and order spare cartridges and backup fuses with the SPDs.