Relays and contactors in Saudi Arabia switch motors and carry control signals in process plants, desalination units and building services. This page covers 60 Hz and 230/400 V coil choices, motor starter coordination, derating in hot panels, SASO and IEC standards, and how to choose a supplier, price and lead time.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified relays & contactors suppliers who quote for your order directly.
Tell us about relays & contactors in Saudi Arabia and receive competitive quotes from verified suppliers — free, fast, and no obligation.
Contactors switch motor and heater loads on command, and relays carry control signals and interlocks between panels, PLCs and field devices. In Saudi Arabia they are specified for pump houses, compressor stations, desalination plants, cement lines, airport and hospital services, and they are part of the circuit protection category in Saudi Arabia because each one is selected with the fuse or breaker that guards it. For solid-state devices and coil-voltage detail, see the companion page on electronic relays and contactors.
| Device | Where it is used in the Kingdom | What to specify |
|---|---|---|
| Power contactor | Motor feeders in process plants and building services | Current by utilisation category, main voltage, coil voltage and frequency |
| Contactor relay | Sequencing and interlocks in control panels | Contacts, coil voltage, terminal type |
| Overload relay | Thermal or electronic protection of motors | Current range, trip class, reset |
| Protection relay | Utility and substation protection logic | Function, EMC compliance, communication |
| Interface relay | Isolates PLC outputs from field loads | Coil voltage, contact current |
For the neighbouring devices see circuit breakers, fuses and fuse links and surge protection devices. Starters are assembled inside motor control centres, which are the usual buyer of high-current contactors.
Specify the coil voltage and frequency from the actual control supply of the panel, and write them on the purchase order. The Saudi grid runs at 60 Hz according to the GCC Interconnection Authority, which links it to the 50 Hz GCC grid through a back-to-back HVDC station, and the country is moving from 127/220 V to 230/400 V supplies, with some older 127 V circuits remaining.
A motor starter divides three jobs: the fuse or breaker clears a short circuit, the contactor switches the motor, and the overload relay trips on sustained overload. IEC 60947-4-1 defines the coordination between them, and type 2 coordination means the starter should be operational after a short circuit.
ABB's fusegear catalogue states that its fused starter solutions provide type 2 coordination to IEC 60947-4-1 up to 690 V, and that aM links are recommended for motor protection. For the Saudi buyer, the practical rule is to select the contactor, the short-circuit device and the overload relay from one coordination table and keep the table with the submittal. The IEC listing says the standard covers electromechanical contactors and starters up to 1,000 V AC or 1,500 V DC. Remember that contactors are not breakers and do not interrupt high fault current on their own.
Rated current falls as ambient temperature rises, and panels in Riyadh, Jubail and Jazan routinely run hot. Siemens's data sheet for the SIRIUS 3RT2036-1AL20 shows AC-1 current of 70 A at 40 degrees C and 60 A at 60 degrees C, AC-3 current of 51 A at 400 V and 24 A at 690 V, an ambient operating range of minus 25 to plus 60 degrees C, and a mechanical life of about 10 million operations.
As of 2026, relays and contactors are specified to IEC standards that SASO adopts, and imported electrical products are handled through SASO and SABER. An Intertek bulletin on the SASO mandatory EMC technical regulation, issued on 17 November 2023 and effective from 17 May 2024, lists SASO IEC 60947-4-1, 60947-4-2 and 60947-4-3 for contactors and controllers, SASO IEC 61810-1 for electromechanical relays and SASO GSO IEC 60255-26 for protection relays. Confirm the current scope with SASO.
| Requirement | Applies to | Authority or source |
|---|---|---|
| SASO IEC 60947-4-1, 4-2, 4-3 | Electromechanical contactors and starters, semiconductor motor controllers, controllers for non-motor loads | SASO, as listed in the Intertek bulletin on the EMC regulation |
| SASO IEC 61810-1 | Electromechanical elementary relays | SASO |
| SASO GSO IEC 60255-26 | EMC for measuring relays and protection equipment | SASO |
| SABER registration | Importers placing regulated products on the market | SASO |
The practical steps for importers are described in the guide to SASO and SABER certificates for industrial equipment.
Panel builders, electrical wholesalers, manufacturer subsidiaries and system integrators supply them in Riyadh, Jeddah and Dammam. Choose a supplier that can issue coordination tables and stock the coils you need.
ListGCC carries makers whose contactor ranges I checked: Siemens with SIRIUS 3RT contactors, ABB with AF contactors, Fuji Electric with the SC series, LS Electric with Metasol contactors, and Chint with the NC1 range. See the sourcing guide, or post your requirement for quotations.
Current rating, pole count, coil type, accessories and bundled overload relays decide the price. Mainstream sizes and standard coil voltages are held by distributors, whereas special coils, large frames and reversing or star-delta kits may be ordered from the factory. Ask for lead time by coil code and keep a spare coil for critical drives.