Pressure switches in Saudi Arabia are devices that change an electrical contact at a set pressure, used to control pumps and compressors, give alarms and trip equipment in oil, gas, water, power and building services. This page explains the types, set point and reset choices, heat and sand limits, SASOEX and SABER scope as of 2026, and which makers supply the Kingdom.
0 suppliers found
Skip the search. Post your requirement and we'll connect you with verified pressure switches suppliers who quote for your order directly.
Tell us about pressure switches in Saudi Arabia and receive competitive quotes from verified suppliers — free, fast, and no obligation.
Saudi plants specify mechanical bellows switches for utilities and package equipment, and electronic switches where a repeatable set point is wanted. They are the on and off devices among pressure instruments for Saudi plants, and are fitted on booster pumps, compressors, hydraulic units, boilers and firewater systems from Riyadh and Jeddah to Jubail and Yanbu.
| Application | Switch used | Setting to define |
|---|---|---|
| Booster and transfer pump control | Mechanical switch with adjustable differential | Cut-in, cut-out and reset |
| Pump dry-run protection | Dual pressure switch with a safety cut-out | Low suction cut-out and restart level |
| Compressor unloading and alarms | Mechanical or electronic switch | High and low pressure points |
| Hydraulic and skid equipment | Electronic switch with PNP outputs | Switch point and switch-back point |
| Boilers and steam | Pressure limiter version with manual reset | Maximum pressure and reset type |
Danfoss describes its KP and KPI switches as used for control, monitoring and alarm systems across industry, with versions for steam boilers and a dual switch for water pump dry-run protection. Endress+Hauser's Ceraphant, an electronic switch, offers one or two PNP switching outputs, with or without a 4 to 20 mA output, and a response time of 20 ms or less. For indication, use pressure gauges; for continuous signals to a DCS, use pressure transmitters.
Choose a switch whose adjustable range puts the set point in the middle of the scale, whose contacts match the circuit it switches, and whose reset type suits the consequence of a trip.
Ceraphant allows the switch point to be set from 0.5 to 100 percent of the upper range in 0.1 percent steps, with a reference accuracy of up to 0.3 percent. A mechanical switch has a coarser scale, so allow for the setting tolerance in the process design.
Heat sets the ambient limit, sand and moisture attack the housing and contacts, and the control voltage and supply frequency of the panel decide whether the contact rating is adequate.
The Danfoss KP data sheet gives minus 40 to plus 65 °C ambient, with up to 80 °C for a maximum of two hours, and minus 40 to plus 100 °C media. Ceraphant PTP31B is rated minus 20 to plus 70 °C ambient. Outdoor skids in the Eastern Province or the Empty Quarter can run hotter than the air, so use sunshades and remote mounting where the set point is close to the limit.
Basic KP switches are IP30 unless fitted in the special IP55 enclosure listed by Danfoss, and Ceraphant lists IP65 to IP67 depending on the connection. For sandstorms, specify a sealed housing, a cable gland suited to the cable and a blanking plug in unused entries.
The Saudi grid is 60 Hz. Contact ratings are given in AC and DC categories, so check the rating at your control voltage, and for DC loads such as solenoids the DC rating is usually much lower than the AC rating.
Pressure switches with electrical contacts are electrical products handled through SABER, and those used in explosive atmospheres fall under the SASOEX certificate. Checked as of 2026; verify the code for your model in SABER.
| Requirement | Applies to | Authority |
|---|---|---|
| SASOEX conformity certificate | Products subject to the Saudi technical regulation for equipment in potentially explosive atmospheres, issued from IECEx or ATEX documents | SASO |
| SABER product and shipment certificates | Regulated electrical products entering the Kingdom, requested by the importer through an approved certification body | SASO |
| BD-142004-01 electrical safety and EMC | Electrical and electronic products on its product list; one route is an IEC CB test report and certificate | SASO |
| Functional safety data | Switches inside safety instrumented functions need failure data from the maker | Plant safety engineer and owner |
| Owner approvals | Aramco, SABIC and utility approved manufacturer lists | The owner |
SASO's page lists the SASOEX certificate among its services and states it is issued from the test certificate and report under IECEx or ATEX. A switch in a classified zone therefore needs its Ex certificate and the Saudi certificate, while a general-purpose switch in a safe area follows the electrical route. Our guide to SASO and SABER certificates sets out the steps. Related controls include relays and contactors, limit switches and safety controllers and relays for trips that must meet safety requirements.
Pressure switches are available from manufacturer entities, authorised instrument distributors and industrial stockists in Riyadh, Jeddah, Dammam and Jubail.
Before award, confirm the brand and model are acceptable to the owner, request Ex and SABER documents where they apply and check local stock. The sourcing guide for Saudi Arabia and the UAE covers supplier checks.
Price depends on type, range, materials, approvals and contact set, and lead time on stock of the exact range and the certificate position.
To receive quotes, post your requirement with medium, range, set points, contact load, reset type, enclosure and area classification.